Anhydrous Ammonia Nurse Tank Testing

Testing Equipment

All testing equipment has been calibrated using standards traceable to the Natinoal Institute of standard and Technology (NIST).

Test Provided

Wagner’s Welding provides DOT certified Anydrous Ammonia Nurse Tank Testing. The test consists of three phases. Each phase must pass in order for the tank to pass. If a tank passes it will need to be tested again in five years. If it fails it cannot be used as a pressure vessel. Phases include:

Visual

The visual Phase consists of visually checking for bulges, dents, gouges, corroded/abraded areas.

Thickness

Test completed using ultrasonic testing equipment at the recommended locations on the tank.

Hydro Test

Tanks are required to be filled with water and hydro tested at 375 PSI for a minimum of 10 minutes. This ensures the integrity of the tank.